FleetZap · Features · Solutions · FleetZap Maintenance · FleetZap Rentals · FleetZap Dispatch · FleetZap GPS Tracking · What a CMMS does · GPS tracking & engine hours · Dispatch & route optimization · Rentals module · Industries · Customers · Resources · Free calculators · Free templates · Pricing · Contact

Chiller maintenance checklist: daily logs, tube cleaning and yearly service

Updated · Reviewed by Israel Margulies, founder and CEO of High Point GPS

A chiller maintenance checklist covers daily log readings (chilled and condenser water temperatures, refrigerant and oil pressures, oil level, motor amps), weekly checks of water quality, leaks and controls, quarterly strainer cleaning, a 6-month controls and oil check, and a yearly shutdown to clean condenser tubes, analyze the oil and leak-test, plus an eddy current tube test every 3 years on water-cooled units. Efficiency depends on clean heat transfer surfaces and readings you can compare over time.

Daily chiller readings catch small drifts

Water-cooled and air-cooled chillers run long hours, and small drifts (dirty condenser tubes, low refrigerant, fouled coils, a sticking valve) raise energy use long before they cause a failure. That’s why daily or per-shift readings are the backbone of chiller maintenance: temperatures, pressures and approach values compared with normal show problems while they’re still cheap to fix.

On top of that come periodic tasks: cleaning condenser tubes or coils, oil analysis, refrigerant leak checks, electrical and control checks, and on water-cooled systems, water treatment and cooling tower care. Refrigerant and major compressor work is usually done by licensed technicians or the manufacturer’s service provider, as local regulations require.

Water-cooled and air-cooled chillers share the refrigerant, oil, electrical and control checks, but the condenser side differs. A water-cooled chiller rejects heat through condenser tubes to a cooling tower, so it adds condenser water readings, water treatment, strainer cleaning, a yearly tube cleaning and periodic eddy current tests of tube walls. An air-cooled chiller rejects heat through finned coils and fans, so its condenser work is keeping coils clean and fans running. The DOE FEMP O&M guide notes that scale in the tubes or air trapped in the condenser raises discharge pressure and compressor power, and that lowering condenser water temperature 2°F to 3°F can raise efficiency by as much as 2% to 3%.

Glycol chillers add a fluid check: measure the freeze point of the water and glycol mix with a refractometer on a regular schedule and correct it with water or glycol. Topping up with premix as water evaporates slowly raises the glycol share, and making up spills with plain water dilutes it; too much glycol cuts capacity, too little can freeze and rupture the evaporator. Use only inhibited glycol, never automotive antifreeze, whose silicate inhibitors can gel on heat transfer surfaces.

Typical chiller maintenance schedule

  • Daily / every shift: Record entering and leaving chilled water temperatures; Record condenser water temperatures or ambient (air-cooled); Record refrigerant pressures, oil pressure and temperature; Compare pressures and oil readings with the normal values in the manual; Check oil level in the sight glass; Check setpoints and turn off or sequence chillers you don't need; Check for alarms, unusual noise or vibration; Check for oil or refrigerant leaks
  • Weekly: Test condenser and chilled water quality for proper chemical balance; Leak-check compressor fittings, oil pump joints and relief valves; Check compressor motor temperature against the manufacturer's spec; Check controls such as hot gas bypass and liquid injection; Check pipe and vessel insulation; Check glycol freeze point with a refractometer (glycol systems; or as often as your manual says)
  • Monthly: Review readings for trends against design; Check chilled and condenser water flow; Clean air-cooled condenser coils as needed; Check water treatment and strainers; Inspect electrical panels for heat or loose connections
  • Quarterly: Clean all water strainers in the chilled and condenser water piping; Have a technician inspect the chiller as the manufacturer recommends; Check purge run time and pumpouts on low-pressure chillers; frequent purging means an air or water leak
  • Every 6 months / seasonal: Oil analysis and refrigerant leak check (licensed technician); Check compressor motor current and insulation; Calibrate sensors and controls; Check vane control, motor load limit and chilled water reset settings; Lubricate vane control linkage and drain the purge vent-line drip leg (centrifugal, per manual); Inspect and clean cooling tower basin and fill (water-cooled); Check starter contacts and safeties
  • Yearly: Clean condenser tubes and inspect evaporator tubes (water-cooled); Send a compressor oil sample to a qualified lab; change oil and filters as specified or when the analysis calls for it; Measure compressor motor winding resistance to ground (qualified technician); Check refrigerant charge, record any refrigerant added and calculate the leak rate; Verify the evaporator refrigerant temperature sensor in an ice bath; Check alignment, seals, oil heater, electrical connections and water flows; Inspect insulation, vibration isolators and piping; Review efficiency and repair history
  • Every 3 years: Eddy current test of condenser and evaporator tubes (water-cooled; more often on critical process chillers); Compare the report with the baseline test to spot thinning tube walls

Chiller daily inspection checklist

  • Chiller running with no alarms
  • Chilled water supply temperature normal
  • Chilled water return temperature normal
  • Condenser water or ambient temperature recorded
  • Evaporator pressure recorded
  • Condenser pressure recorded
  • Oil pressure and level normal
  • No oil or refrigerant stains at fittings
  • No unusual noise or vibration
  • Water flow switches and pumps running
  • Control panel readings recorded
  • Mechanical room clean and ventilated
  • Motor amps per phase and % of rated load amps recorded
  • Run hours and number of starts recorded
  • Chilled and condenser water pressure drop recorded
  • Purge run time and pumpouts recorded (low-pressure chillers)

What fails on chillers, and how to prevent it

  • Condenser tubes or coils: High condenser pressure and approach, rising energy use. Keep water treatment in control, clean tubes yearly and coils as often as the site requires
  • Refrigerant charge: Low evaporator pressure, poor cooling, oil stains. Have licensed technicians leak-check on schedule and repair leaks promptly
  • Compressor and oil system: Low oil pressure, high discharge temperature, noise. Analyze oil, change filters and oil as specified and track trends
  • Water flow and pumps: Flow-switch trips, freeze-protection alarms. Clean strainers, check pumps and verify flow
  • Controls and sensors: Short cycling, wrong setpoints, nuisance alarms. Calibrate sensors and check controls regularly
  • Glycol mix (glycol chillers): Freeze point reading too high, freeze alarms, loss of capacity. Check the freeze point with a refractometer, correct it with water or inhibited glycol and never use automotive antifreeze
  • Air or moisture in the refrigerant (low-pressure chillers): Frequent purge pumpouts, high condenser pressure. Log purge run time and have a technician find and fix the leak quickly
  • Heat exchanger tube walls: Tube leak, water in the refrigerant or oil. Eddy current test the tubes on the manufacturer's interval and plug or replace flagged tubes

Tracking chillers in FleetZap

Each chiller’s record holds its building, make, model, serial, refrigerant type and warranty dates, with an alert before the warranty ends.

A daily log procedure records temperatures and pressures as readings with limits. Anything outside the range counts as a fail and creates a repair job.

Monthly, semi-annual and annual service run on calendar schedules and open with the right procedure.

Refrigerant work, oil analysis and tube cleaning go to contractors as vendor work orders, with the cost charged to the chiller.

Pressure vessel or refrigerant certificates, where your jurisdiction requires them, are compliance items, and admins hear about them before the expiry date.

The 3-year eddy current test and the yearly shutdown run as date-based schedules, so the work order opens on time with the steps attached.

Pounds of refrigerant added, oil analysis results and the technician's notes go into the work order, so the leak history and three years of records sit on the chiller's own page.

Free tools for this

Sources

FleetZap Maintenance

Work orders, PM, parts, compliance, assets and KPIs. Explore FleetZap Maintenance.

Frequently asked questions

How often should a chiller be serviced?

Most chillers get daily readings, monthly checks, a semi-annual service and a major annual service with tube cleaning or coil cleaning, but follow the manufacturer’s manual and local regulations. Critical or heavily loaded chillers may need more frequent attention.

Why keep a daily chiller log?

Readings compared over time show fouling, refrigerant loss and control problems early. A rising condenser approach, for example, often points to dirty tubes. Recording readings in the same procedure every day makes trends easy to spot.

How often should condenser tubes be cleaned?

Many water-cooled chillers have condenser tubes cleaned yearly, but water quality drives it. If condenser approach temperature rises, the tubes may need cleaning sooner. Follow the manufacturer and your water treatment provider.

Who can work on chiller refrigerant?

In most places only licensed or certified technicians may handle refrigerant. Many owners use a contractor for refrigerant and major compressor work and track it as a vendor work order.

What is on a chiller maintenance checklist?

Daily: chilled and condenser water temperatures, refrigerant and oil pressures, oil level, amps, alarms and leaks. Weekly: water quality, leak checks at fittings, controls and insulation. Quarterly: strainers. Every 6 months: control settings, oil analysis, leak check. Yearly: tube cleaning, oil and electrical checks, sensor calibration. Every 3 years: eddy current tube testing on water-cooled units. Follow your chiller's manual first.

How do you maintain a glycol chiller?

Do everything a water chiller needs, plus check the glycol mix. Measure the freeze point with a refractometer on a regular schedule, keep it as far below the lowest setpoint or outdoor temperature as the manual says (one manufacturer specifies 25°F below), and correct it with water or inhibited glycol. Too much glycol cuts capacity; too little can freeze the evaporator. Never use automotive antifreeze.

What are the EPA refrigerant leak repair rules for chillers?

Under 40 CFR 82 Subpart F, a chiller with 50 lb or more of an ozone-depleting refrigerant (CFC or HCFC) must have leaks repaired within 30 days once its leak rate passes 10% a year for comfort cooling, 20% for commercial refrigeration or 30% for industrial process refrigeration, followed by verification tests. Since January 1, 2026, 40 CFR 84 Subpart C applies the same thresholds to appliances with 15 lb or more of HFC or other high-GWP substitute refrigerant, adds a leak rate calculation each time refrigerant is added, a report when a unit leaks 125% of its charge in a calendar year, and three years of records. Check the regulation for when it applies to your chillers.

What's the difference between water-cooled and air-cooled chiller maintenance?

Water-cooled chillers add condenser water treatment, strainer cleaning, cooling tower care, yearly condenser tube cleaning and eddy current tube tests. Air-cooled chillers skip those and instead need condenser coil cleaning and fan checks.